Online dynamic load modeling has become possible with the availability of Static Voltage Compensator (SVC) and Phasor Measurement Unit (PMU) devices. The power of the load response to the small random bounded voltage fluctuations caused from SVC can be measured by PMU for modelling purposes. The aim of this paper is to illustrate the capability of identifying an aggregated load model from high voltage substation level in the online environment. The induction motor is used as the main test subject since it contributes the majority of the dynamic loads. A test system representing simple electromechanical generator model serving dynamic loads through the transmission network is used to verify the proposed method. Also, dynamic load with multiple induction motors are modeled to achieve a better realistic load representation.

History

Related Materials

  1. 1.
    DOI - Is published in 10.1109/APPEEC.2015.7381020
  2. 2.
    ISBN - Is published in 9781467381338 (urn:isbn:9781467381338)

Start page

894

End page

898

Total pages

5

Outlet

Proceedings of the 7th IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC 2015)

Name of conference

APPEEC 2015

Publisher

IEEE

Place published

United States

Start date

2015-11-15

End date

2015-11-18

Language

English

Copyright

© 2015 IEEE

Former Identifier

2006063459

Esploro creation date

2020-06-22

Fedora creation date

2016-07-20

Usage metrics

    Scholarly Works

    Exports

    RefWorks
    BibTeX
    Ref. manager
    Endnote
    DataCite
    NLM
    DC