RMIT University
Browse

Impacts of storey number of buildings on solar chimney performance: A theoretical and numerical approach

journal contribution
posted on 2024-11-02, 21:40 authored by Haihua Zhang, Yao Tao, Guomin ZhangGuomin Zhang, Jie LiJie Li, Sujeeva SetungeSujeeva Setunge, Long ShiLong Shi
Under the fact that solar chimney was less investigated in multi-storey buildings, a theoretical model was then developed for solar chimney-induced buoyancy-driven natural ventilation. This is the first study addressing the influences of the storey number on ventilation rates for multi-storey solar chimney (SC) buildings. A storey correction coefficient was proposed to predict the SC-induced ventilation at various floors with identical air inlet areas. The theoretical model was established to elucidate the relationship among ventilation flow rates, solar radiation intensity, vent sizes and storey number (f), where the numerical results have also been validated. Although the total SC ventilation performance is enhanced, its enhancement with a higher chimney cavity was less effective when compared to those solar chimneys in single-storey buildings. This is due to the higher chimney cavity hindering the ventilation performance of the lower floors. The volume flow rate decreased exponentially for the top floors of each building when the two-storey building increased to a seven-storey building. For buildings with more than three storeys, the overall volume flow rate was more sensitive to the cavity gap than the solar radiation intensity, with an improvement in ventilation by 45.6% compared to 26.0% under the same conditions, respectively. To maximize the total flow rate, the optimal cavity gap should increase gradually from 0.2 m to 1.5 m for single-to seven-storey buildings. The findings of this study contribute to a further application of solar chimneys in multi-storey buildings.

Funding

Next-generation, prefabricated, modular, solar heating and cooling system

Australian Research Council

Find out more...

History

Related Materials

  1. 1.
    DOI - Is published in 10.1016/j.energy.2022.125200
  2. 2.
    ISSN - Is published in 03605442

Journal

Energy

Volume

261

Number

125200

Start page

1

End page

12

Total pages

12

Publisher

Elsevier

Place published

United Kingdom

Language

English

Copyright

© 2022 Elsevier Ltd. All rights reserved.

Former Identifier

2006118409

Esploro creation date

2023-01-12